Strona 1 - Water/Glycol Cooled

Modular Data Temp SystemsAir CooledWater/Glycol Cooled8, 10 and 13 ton capacitiesR-407CISO 9001 Certifi ed

Strona 2

10Site ControlSite Monitoring DevicesDARA-4 - Data Aire Relay Auto Changeover controller allows for unit rotation and backup capabilities while interf

Strona 3

11Options1” Pre-Filter - Units may be ordered with a one inch pre-fi lter.Pump Package - Centrifugal pump packages are available to circulate water or

Strona 4 - MODULAR DATA TEMP

12R-407CMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 CAPACITY in Btu/hr - gross80° DB/67° WB 50% RH Total 105,800 134,000 163,800 Sensible 84,

Strona 5 - Table of Contents

13 R-407CAIR COOLED: Performance data at STANDARD airfl owMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 ELECTRICAL SECTION Standard Moto

Strona 6 - Modular Data Temp

14R-407CAIR COOLED: Performance data at STANDARD airfl owMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 ELECTRICAL SECTION Next Size MotorEle

Strona 7 - REFRIGERATION CIRCUIT

15 R-407CMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 CAPACITY in Btu/hr - gross80° DB/67° WB 50% RH Total 108,700 138,700 168,800

Strona 8

16R-407CAIR COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 ELECTRICAL SECTION Standard motorEl

Strona 9

17 R-407CAIR COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER DTAD/U-08 DTAD/U-10 DTAD/U-13 ELECTRICAL SECTION Next size motorElectrical

Strona 10 - Site Monitoring Devices

18R-407CMODEL NUMBER DTWD/U-08 DTWD/U-10 DTWD/U-13 CAPACITY in Btu/hr - gross80° DB/67° WB 50% RH Total 109,900 139,400 170,200 Sensibl

Strona 11

19 R-407CWATER/GLYCOL COOLED: Performance data at STANDARD airfl ow CONDENSER WATER (Maximum design water pressure 150 psi - High pressure valves op

Strona 13

20R-407CMODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13 ELECTRICAL SECTION Standard MotorElectrical data based on: electric reheat

Strona 14

21 R-407CMODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13 ELECTRICAL SECTION Next Size MotorElectrical data based on: electric rehea

Strona 15

22R-407CMODEL NUMBER DTWD/U-08 DTWD/U-10 DTWD/U-13 CAPACITY in Btu/hr - gross80° DB/67° WB 50% RH Total 113,600 144,100 176,300 Sensible

Strona 16

23 R-407CMODEL NUMBER DTWD/U-08 DTWD/U-10 DTWD/U-13 CONDENSER WATER Maximum design water pressure 150 psi - High pressure valves optionalUsing 6

Strona 17

24R-407CWATER/GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13 ELECTRICAL SECTION Standard MotorEle

Strona 18

25 R-407CWATER/GLYCOL COOLED: Performance data at OPTIONAL airfl owMODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13 ELECTRICAL SECTION Next Size MotorE

Strona 19

26MODULAR DATA TEMP 8, 10, and 13 ton, Downfl ow

Strona 20

27MODULAR DATA TEMP 8, 10, and 13 ton, Upfl ow

Strona 21

28Air Cooled Condensers • DARC 06-21 Single Circuit

Strona 22

29Air Cooled Condensers • DARC 06-21 Single Circuit

Strona 23

… the pioneer and builder of the most complete line of precision cooling equipmentBack in the late 1960’s and early 70’s with the advancement of the c

Strona 24

30Fluid Coolers • DAFC MODEL 06-50

Strona 25

31Fluid Coolers • DAFC MODEL 06-50

Strona 26

32DATA AIRE Piggy Back Heat Exchanger • DAFC and DARC 6, 7, and 9 ton

Strona 27

33DATA AIRE Piggy Back Heat Exchanger • DAFC and DARC 11, 15 and 17 ton

Strona 28

34Floorstand and Plenums

Strona 29

35Model Number Identifi cationModel Number Identifi cation

Strona 30

36MODULAR DATA TEMP SERIES • Dimensional Weight and Data - Air CooledMODULAR DATA TEMP SERIES DIMENSIONAL and WEIGHT DATA - AIR COOLEDDownfl ow and Upfl

Strona 31

37 MODULAR DATA TEMP SERIES8, 10, 13 ton DX UnitsGuide Specifi cationsGENERALThe environmental control units shall be provided with a high sensible coo

Strona 32

38Air Cooled with Floor Mounted Indoor Condenser - The refrigeration system shall be split type with an indoor evaporator sec-tion and fl oor mounted i

Strona 33

39GUIDE SPECIFICATIONS, continuedon all three power lines, internal thermostats for winding protection, crankcase heater, sight-glass, condenser with

Strona 34 - Floorstand and Plenums

MODULAR DATA TEMPAir CooledWater/Glycol CooledR-407CSingle Circuit DesignCompact Size for Easy ManeuverabilityProduct DescriptionPerformance/Electrica

Strona 35 - Model Number Identifi cation

40Data Aire Data Alarm Processor III ( DAPTM III)The environmental system shall be furnished with a microprocessor based Data Alarm Processor-III pane

Strona 36

41GUIDE SPECIFICATIONS, continued The following historical data shall be available: High temperature last 24 hours Low temperature last 24 hours Eq

Strona 37

42OPTIONSRemote Temperature and Humidity SensorsUnits shall be provided with remote temperature and humidity sensors. Sensors shall be provided in a

Strona 38

43pump changeover in the event of a pump failure. Upon pump changeover, a message “Standby Pump On” shall be displayed on the indoor unit microproces

Strona 39

230 W. BlueRidge AvenueOrange, CA 92865800-347-2473www.dataaire.com e-mail: [email protected] Member of the CS Group of CompaniesData Aire, Inc

Strona 40

Table of ContentsDesign Features ...7Refr

Strona 41

6PRECISION COOLINGModular Data Temp Series units are precision environmental control systems that bring a standard of reliable performance to today’s

Strona 42

7FILTER SECTIONUnits are provided with 4 inch deep, 30% effi cient fi lters (based on ASHRAE Std. 52.1-92). The fi lter section is accessible from the t

Strona 43

8DATA ALARM PROCESSOR-IIIThe Data Alarm Processor-III (DAP™ III) offers the defi nitive answer for precision environmental control. The DAP-III control

Strona 44 - Orange, CA 92865

9PROTECTIVE and SAFETY FEATURESMetal shell enclosure with sealed front control panel Watch dog timerOpto-coupler signal inputs Protected 24VAC power